Converting to another build¶
On this page: why a build change is never an update, the procedure on site, and what to check afterwards.
Why only by a full reflash¶
A box refuses any update of another build or another board, remotely and over USB (other build,
other board). There is no exception, also not with a forced or downgrade update. This guarantees that:
- a read box can never receive or install switching firmware by accident;
- a switching box never silently falls back to read firmware through an update;
- firmware for one board never lands on the other.
The only way to change build is a complete reflash over USB on site, with an explicit choice of board and build.
| From | To | Possible |
|---|---|---|
poe_8di8do read |
poe_8di8do switching |
Yes, full flash on site |
poe_8di8do switching |
poe_8di8do read |
Yes, full flash on site |
rs485_can read |
switching | No: the RS485-CAN board has no outputs |
| Any board | Other board | No: different hardware |
Procedure¶
- Before you start: for read to switching, the electrical installation (interposing relays or contactors, hardware interlocks) must be done and checked by a licensed electrician. See Electrical installation and safety. Disconnect the DO wiring until the new firmware runs and the outputs are configured.
- Note the box's current settings that you want to keep (bus devices, input roles, network).
- Run a full flash with the web flasher and choose the target board and build explicitly.
- Register the box again (the full flash erases its identity).
- Configure it again on the setup page: bus devices, inputs, network. For the switching build also the output functions. See Switching build.
- Check the build on the setup page or the USB console status line (
build switching, board poe_8di8do). - Reconnect the DO wiring and test each output function with the electrician present.
- In the portal, the Remote panel shows the box as switching build.
To be confirmed
How re-registration after a full flash is done (by Lutra or by the partner), and whether the pairing code stays the same, is not decided yet.
Boxes with firmware older than build identities¶
Firmware up to 0.2.x does not check the build identity and does not report its board. When updating such a box, choose the correct channel yourself (the web flasher asks explicitly). From the first version with build identity onwards the box checks it itself.
Related pages¶
Last reviewed: 2026-11-24. Applies to Lutra Lite 0.4.1.