Electrical installation and safety¶
Draft: review by a qualified electrician required before publication
This chapter states structure and general, conservative principles only. It must be reviewed and signed off by a qualified electrician before it is published or used for an installation.
All work on mains voltage must be done by a licensed electrician under local regulations, for example NEN 1010 in the Netherlands and IEC 60364 generally (including its part on swimming pools).
Lutra supplies low-voltage control electronics. Lutra is not responsible for mains wiring, earthing/bonding of the pool installation, or the selection of contactors/relays for loads.
On this page: the responsibility boundary, who does which work, the voltage zones in a plant room, how outputs must be connected through interposing relays, inputs, earthing and isolation, and a checklist before energising. Values that depend on local regulations (cable cross-sections, RCD ratings, clearances, protection classes, zones) are deliberately not given here.
Responsibility boundary¶
| Lutra supplies and is responsible for | Lutra is not responsible for |
|---|---|
| The Lutra Lite firmware and its documented behaviour | Mains wiring of any kind |
| Documentation of the box's low-voltage interfaces (RS485, digital inputs, digital outputs, power input) | Earthing and equipotential bonding of the pool installation |
| The safety logic in the firmware of the switching build, as documented | Selection, rating and installation of contactors, interposing relays, motor protection, fuses and RCDs |
| The power supply that feeds the box, its installation and its protection | |
| Compliance of the complete installation with local regulations and the manufacturer instructions of the pool equipment | |
| Hardware interlocks in the installation (they are required for the switching build, but designing and wiring them is the electrician's work) |
The pool equipment (controllers, chlorinators, pumps, heat pumps) remains responsible for its own safety functions. Lutra never takes over or bypasses them.
Who does what¶
| Work | Who |
|---|---|
| Mounting the box on the DIN rail, network cable, RS485 bus cable, potential-free contacts on DI | Installer or technician, provided no mains voltage is involved |
| Power supply for the box, if fed from mains | Licensed electrician |
| Interposing relays and contactors for loads, their supply and protection | Licensed electrician |
| Hardware interlocks (flow contact, dry-run contact, level contacts in series) | Licensed electrician |
| Earthing and equipotential bonding | Licensed electrician |
| Testing and documenting the installation before use | Licensed electrician, according to local regulations |
Voltage zones¶
Think of the installation as two zones that must stay separated:
| Zone | Contains |
|---|---|
| Low-voltage control | The Lutra box (7 to 36 V DC, PoE or 5 V USB-C), RS485 bus, digital inputs, the DO outputs and the relay coils they drive, Lutra measuring modules |
| Mains and power | Supply of the box's power supply, pumps, heat pumps, heaters, lighting transformers, valves on mains voltage, contactor main contacts |
- Interposing relays and contactors form the boundary: their coil is in the low-voltage zone, their switching contacts in the mains zone.
- Lutra's own pH/ORP module is designed to be fully SELV: fed from a certified SELV supply of 12 to 24 V DC, with nothing on the module touching mains voltage.
To be confirmed by electrician
- Required class of the power supply for the box (SELV or PELV) and its protection.
- Separation between low-voltage and mains wiring in the same cabinet (routing, separate ducts, clearances, insulation ratings).
- Requirements for the enclosure (IP rating, location relative to the pool zones). The retrofit measuring kit design uses an IP65 enclosure, optionally with conformal coating on the electronics.
Outputs and interposing relays¶
This section applies only to the switching build. The read build never switches.
Never connect a load directly to the DO terminals
The DO outputs of the 8DI-8DO board are Darlington open-collector (sink) outputs, rated at most 500 mA, with a flyback diode. They may only drive the coil of an interposing relay or a contactor coil on a low-voltage supply, never a pump, valve, heater or any mains load directly.
The board's factory firmware switches the outputs (all outputs on at start-up, inputs mirrored to outputs). Until Lutra firmware is on the board, connect nothing to the DO terminals. The Lutra read build never switches an output.
Principles from the board's specification:
- The DO outputs are open-collector sink outputs (Darlington with optocoupler), at most 500 mA, with a flyback diode. The COM terminal goes to the plus of the coil supply, so the flyback diode works.
- Each output drives only the coil of an interposing relay or a DC contactor coil. The relay's contacts, or a contactor driven by it, switch the load.
- Hardware interlocks are required in addition to the firmware interlocks:
- heating enable: the flow contact in series with the coil of the enable relay;
- pump: the dry-run contact (
level_low) in series with the pump start, where the pump allows it; - refill: preferably a float valve or the
level_highcontact in series with the valve.
- Recommended: an auxiliary contact of the pump contactor back to a digital input (
pump_feedback), so the firmware sees whether the pump really runs. - Dosing pumps are not supported by any Lutra build. Where peristaltic pumps are switched in a future build, they must go through a contactor or interposing relay, never directly on a DO.
To be confirmed by electrician
- Types of interposing relays (coil voltage, contact rating, utilisation category for motor and inductive loads, relay modules with or without built-in diode).
- When an interposing relay is enough and when a contactor with motor protection is required.
- Behaviour of variable-speed pumps with digital speed inputs: whether those inputs are potential-free and can be driven by relay contacts directly.
- Wiring diagrams for each output function and each hardware interlock.
Digital inputs¶
- The inputs are optically isolated and intended for contacts. A contact closed between DIx and the GND of the input block reads as active.
- Use potential-free contacts (auxiliary contacts, float switches, flow switches).
- Never connect mains voltage to an input.
To be confirmed by electrician
- Whether active (powered) input signals may be used, and within which voltage range (not yet measured).
- How to bring an auxiliary contact from a contactor in the mains zone to the input safely.
Earthing and isolation¶
What the sources establish:
- The RS485 and CAN interfaces of both boards are isolated. The digital inputs and outputs of the 8DI-8DO board are optically isolated.
- Lutra's pH/ORP module isolates the probe side from the host side (power and data). That isolation is functional, with both sides SELV: the water side and the 24 V side must not share an earth or reference. A leaking temperature sensor on the probe side would create a second path to the measuring reference, which is why its sensor sits on the host side.
- On a Jandy/AquaLink bus, connect only A, B and 0V, never POS (the panel's supply).
To be confirmed by electrician
Must be earthed or bonded: which parts of the pool installation require equipotential bonding and protective earth, and whether any part of the Lutra installation (enclosure, DIN rail, power supply) must be connected to it.
Must not be earthed: whether the 0 V of the box, the RS485 0 V, the probe reference of measuring modules or the shield of the bus cable may be connected to protective earth, and where a cable shield is terminated.
RCD protection and other protective devices for the supply circuits.
Before energising¶
- Mains work done and tested by a licensed electrician, with documentation according to local regulations.
- Lutra firmware is on the board before anything is connected to the DO terminals.
- No load connected directly to a DO terminal; only relay or contactor coils within 500 mA.
- Hardware interlocks wired as required for every assigned switching function.
- Low-voltage and mains wiring separated as decided by the electrician.
- Only potential-free contacts on the digital inputs.
- On a Jandy bus, POS not connected.
Continue with the Commissioning checklist.
Related pages¶