Wiring the box¶
On this page: mounting, power, network, the RS485 bus, digital inputs and the outputs. Read Electrical installation and safety first.
Mains work only by a licensed electrician
Any work on mains voltage (230/400 V), on the supply of pumps, heaters, heat pumps and lighting, on contactors and interposing relays switching those loads, and on earthing and equipotential bonding of the pool installation must be done by a licensed electrician under local regulations (for example NEN 1010 in the Netherlands, IEC 60364 generally). See Electrical installation and safety.
Overview¶
The schematic shows the low-voltage connections of an 8DI-8DO box. The RS485-CAN board has only the power and RS485 connections. The sections below give the rules for each connection.
Mounting¶
Mount the box on the DIN rail in the plant room. On the 8DI-8DO board, connect the external Wi-Fi antenna (U.FL) if Wi-Fi is used.
Power¶
| Board | Options |
|---|---|
| 8DI-8DO | 7 to 36 V DC on the screw terminal, or PoE (802.3af) over the network cable, or 5 V via USB-C |
| RS485-CAN | 7 to 36 V DC; do not power it via USB-C at the same time |
Network¶
A network cable is preferred (8DI-8DO only); with PoE one cable carries data and power. Wi-Fi is the fallback. See Network.
RS485 bus¶
- Connect RS485 A and B, and 0V (GND), to the bus of the pool equipment.
- All devices on one bus must use the same baud rate, parity and stop bits. See Bus devices and inputs.
- Termination resistor (120 ohm) only on the last device of the bus.
- Jandy/AquaLink bus: connect only A, B and 0V, never POS (the panel's supply). Wire colours on that bus: A black, B yellow or white, 0V green, POS red.
- If the bus already has a master (PLC, control panel), Lutra may only listen. See Listen-only mode.
To be confirmed
- Terminal layout of the boards (where A, B and GND are).
- Whether the 120 ohm jumper on the Lutra box must be set (depends on its position on the bus).
- Cable type and maximum cable length.
Digital inputs (8DI-8DO)¶
- Connect potential-free contacts between an input DI1 to DI8 and the GND of the input block. A closed contact reads as active.
- Typical uses: flow switch, pump running (auxiliary contact), level floats, leak sensor, fault contact of a heat pump or chlorinator, plant room door.
- Prefer NC contacts for flow and low level, so a broken wire reads as an alarm.
- The flow switch goes on DI1 in the current installation guide. See Flow switch.
Assign the role of each input on the setup page. See Digital inputs.
Digital outputs (8DI-8DO)¶
Never connect a load directly to the DO terminals
The DO outputs of the 8DI-8DO board are Darlington open-collector (sink) outputs, rated at most 500 mA, with a flyback diode. They may only drive the coil of an interposing relay or a contactor coil on a low-voltage supply, never a pump, valve, heater or any mains load directly.
The board's factory firmware switches the outputs (all outputs on at start-up, inputs mirrored to outputs). Until Lutra firmware is on the board, connect nothing to the DO terminals. The Lutra read build never switches an output.
With the read build: leave the DO terminals unconnected. With the switching build: see Outputs and interposing relays.
Pin header¶
The pin header has IO1, IO0, RXD, TXD, SDA, SCL, GND and VCC. Do not connect anything to SDA/SCL (they carry the clock and the output expander) or IO0 (a strapping pin).
To be confirmed
A second RS485 port through an isolated TTL-to-RS485 module on RXD/TXD is designed but not supported by the firmware yet. A DS18B20 temperature sensor on the free IO1 is a possibility, not a supported feature.
Related pages¶
Last reviewed: 2026-11-24. Applies to Lutra Lite 0.4.1.